-40%
XCKP2118G11 LIMIT SWITCH, 1NO/1NC 10A
$ 23.76
- Description
- Size Guide
Description
Mainrange of product
OsiSense XC
series name
Standard format
product or component type
Limit switch
device short name
XCKP
sensor design
Compact form A CENELEC EN 50047
body type
Fixed
head type
Rotary head
material
Plastic
body material
Plastic
head material
Zamak
fixing mode
By the body
movement of operating head
Rotary
type of operator
Spring return roller lever thermoplastic
type of approach
Lateral approach, 2 directions
number of poles
2
contacts type and composition
1 NC + 1 NO
contact operation
Snap action
Complementary
tracks
24/40 mm
switch actuation
By 30° cam
electrical connection
Screw-clamp terminals 1 x 0.34...2 x 1.5 mm²
cable entry
1 entry tapped for Pg 11 cable gland
contacts insulation form
Zb
positive opening
With
positive opening minimum torque
2.21 lbf.in (0.25 N.m)
minimum torque for tripping
0.89 lbf.in (0.1 N.m)
minimum actuation speed
0.03 ft/s (0.01 m/s)
maximum actuation speed
4.92 ft/s (1.5 m/s)
repeat accuracy
0.1 mm on the tripping points with 1 million operating cycles
contact code designation
A300, AC-15 (Ue = 240 V), Ie = 3 A 10 A EN/IEC 60947-5-1 appendix A
Q300, DC-13 (Ue = 250 V), Ie = 0.27 A EN/IEC 60947-5-1 appendix A
[Ui] rated insulation voltage
300 VUL 508
500 V 3)IEC 60947-1
300 VCSA C22.2 No 14
maximum resistance across terminals
25 MOhm IEC 60255-7 category 3
[Uimp] rated impulse withstand voltage
6 kV IEC 60664
6 kV IEC 60947-1
short-circuit protection
10 A cartridge fuse gG
electrical durability
5000000 cycles, DC-13, 120 V, 4 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C
5000000 cycles, DC-13, 24 V, 10 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C
5000000 cycles, DC-13, 48 V, 7 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C
mechanical durability
10000000 cycles
width
1.22 in (31 mm)
height
2.56 in (65 mm)
depth
1.18 in (30 mm)
net weight
0.30 lb(US) (0.135 kg)
terminals description ISO n°1
(13-14)NO
(21-22)NC
Environment
shock resistance
50 gn 11 ms IEC 60068-2-27
vibration resistance
25 gn 10…500 Hz)IEC 60068-2-6
IP degree of protection
IP66 IEC 60529
IP67 IEC 60529
IK degree of protection
IK04 EN 50102
electrical shock protection class
Class II IEC 61140
Class II NF C 20-030
ambient air temperature for operation
-13…158 °F (-25…70 °C)
ambient air temperature for storage
-40…158 °F (-40…70 °C)
protective treatment
TC
product certifications
CSA
CCC
UL
standards
CSA C22.2 No 14
EN 60204-1
UL 508
EN 60947-5-1
IEC 60204-1
IEC 60947-5-1